Check valves GAR type CHV has been designed to be used on refrigerantion and air conditioning system, on liquid and suc tion line. Their installation avoid the risk of flow inversion.

Materials
Brass CW617N Obturator CW614N Oring HNBR

Installation
They can be mounted also in a vertical or horizontal position. The system must be clean before the assembly because they are sensitive to impurities. We recommend to use a soldering league with low fusion point during the soldering process of the check valve CHV on the system. During this process do not point the flame directly towards the body to avoid compromis ing the seal of the internal gaskets

Operating conditions
TS -40°C + 150°C PS 30 bar
Refrigerant fluids: HFC, HFO, blends Available on demand for HC e CO2